产品介绍 Burner controls of the LMG... range are used for the startup and supervision of singleor 2-stage gas or gas / oil burners in intermittent operation. The flame is supervised with an ionisation probe or UV flame detector QRA... (with ancillary unit AGQ2...A27). LMG21... / LMG22... in the same housing replace burner controls LGB21... / LGB22...(refer to Type summary) and, using the adapters, burner controls LFI7... and LFM1...(refer to Ordering). Detection of undervoltages Air pressure supervision with functional test of air pressure monitor during startup and operation Electrical remote reset Display of error code and flame ** by LEDs in the lockout reset button Accurate program sequence owing to the digital processing of **s LMG49... for atmospheric gas burners 型号表 型号 tw/s t1/s TSA/s t3n/s t3/s t4/s t10/s t11/s t12/s LMG21.130A27 2.5 7 3 2 2 8 5 - - LMG21.230A27 2.5 20 3 2 2 8 5 - - LMG21.330A27 2.5 30 3 2 2 8 5 - - LMG21.350A27 2.5 30 5 4 2 10 5 - - LMG21.550A27 2.5 50 5 4 2 10 5 - - LMG22.130A27 2.5 7 3 2 3 8 3 12 12 LMG22.230A27 2.5 20 3 2 3 8 3 16.5 16.5 LMG22.233A27 2.5 20 3 2 3 8 3 30 30 LMG22.330A27 2.5 30 3 2 3 8 3 12 11 LMG25.230A27 2.5 20 3 2 2 8 5 - - LMG25.330A27 2.5 30 5 4 2 10 5 - - LMG25.350A27 2.5 30 5 4 2 10 5 - - LMG49.030B27 2.5 1 3 2 0.5 0.5 - - - tw 等待时间 t1 预吹扫时间 TSA 点火安全时间 t3 预点火时间 t3n 后点火时间 t4 电磁阀1到电磁阀2的间隔时间,或电磁阀1到比例控制开始的间隔时间 t10 空气压力信号建立时间 t11 伺服马达程序打开时间 t12 伺服马达程序关闭时间 技术参数 主要参数 主电压 AC220V -15%+10% 主频率 50...60Hz ±6% 外部保险丝 10A 功率 12VA 重量 160g 保护等级 IP40 环境条件 运输环境 IEC 721-3-2 内部条件 class 2K2 温度范围 -40...+60oC 湿度 <95% 运行环境 IEC 721-3-3 内部条件 class 3K5 机械条件 class 2M2 温度范围 -20...+60oC 湿度 <95% 不得进水